High efficiency, maximum uptime and quick installation
With 100 years of industry experience and correspondingly high-quality products, the company Volvo Penta is one of the world’s most famous manufacturers of diesel engines. A Volvo Penta power generator is characterized by unrivaled load capacity and fast start-up capability. The highly efficient motors guarantee low operating costs due to low amounts of oil, high quality and reliability as well as easy installation. Maintenance intervals can last up to 1,000 hours.
Volvo Penta engines are extremely economical and flexible. They meet all G3 requirements according to ISO8528-5.
Our Volvo power generators: 1.500 r.p.m – 50 Hz – diesel – watercooled
Volvo Penta Generator Model |
kVA 100 % PRP* |
Motortype |
WA-V 85 | 85 | TAD530GE |
WA-V 100 | 100 | TAD531GE |
WA-V 130 | 130 | TAD532GE |
WA-V 150 | 150 | TAD731GE |
WA-V 180 | 180 | TAD732GE |
WA-V 200 | 200 | TAD733GE |
WA-V 250 | 250 | TAD734GE |
WA-V 300 | 300 | TAD1341GE |
WA-V 350 | 350 | TAD1342GE |
WA-V 380 | 380 | TAD1343GE |
WA-V 400 | 450 | TAD1344GE |
WA-V 450 | 450 | TAD1345GE |
WA-V 500 | 500 | TAD1641GE |
WA-V 600 | 595 | TAD1642GE |
WA-V 620 | 620 | TWD1643GE |
WA-V 640 | 640 | TWD1643GE |
WA-V 660 | 660 | TWD1644GE |
WA-V 700 |
700 | TWD1645GE |
*Prime Power PRP. Maximum power for variable load, no time limit per year. The average 24 hours operation should not exceed 80% of that power. For control purposes and start-up of heavy machinery an overload of 10% is permissible for 1 hour within 12 hours. Operating mode according to ISO 8528. The maintenace is to be considered.
Volvo Penta Generator |
Power KWm. |
Consumption 100 % Last PRP |
WA-V 85 | 74 KW | 19,00 L/h |
WA-V 100 | 88 KW | 23,00 L/h |
WA-V 130 | 112 KW | 29,00 L/h |
WA-V 150 | 133 KW | 34,00 L/h |
WA-V 180 | 160 KW | 41,00 L/h |
WA-V 200 | 177 KW | 46,00 L/h |
WA-V 250 | 217 KW | 52,00 L/h |
WA-V 300 | 275 KW | 68,00 L/h |
WA-V 350 | 303 KW | 68,00 L/h |
WA-V 380 | 325 KW | 82,00 L/h |
WA-V 400 | 354 KW | 83,00 L/h |
WA-V 450 | 388 KW | 92,00 L/h |
WA-V 500 | 430 KW | 102,00 L/h |
WA-V 600 | 503 KW | 117,00 L/h |
WA-V 620 | 536 KW | 120,00 L/h |
WA-V 640 | 536 KW | 124,00 L/h |
WA-V 660 | 555 KW | 130,00 L/h |
WA-V 700 | 640 KW | 139,00 L/h |
Volvo Penta Generator |
Datasheet |
WA-V 85 | |
WA-V 100 | |
WA-V 130 | |
WA-V 150 | |
WA-V 180 | |
WA-V 200 | |
WA-V 250 | |
WA-V 300 | |
WA-V 350 | |
WA-V 380 | |
WA-V 400 | |
WA-V 450 | |
WA-V 500 | |
WA- 600 | |
WA-V 620 | |
WA-V 640 | |
WA-V 660 | |
WA-V 700 |
“G” on open frame
Stationary version (open type) frame “G”
Volvo Penta Generator | Fueltank L |
Length mm |
WA-V 85 “G” | 195 | 2.050 |
WA-V 100 “G” | 210 | 2.050 |
WA-V 130 “G” | 210 | 2.250 |
WA-V 150 “G” | 220 | 2.500 |
WA-V 180 “G” | 230 | 2.500 |
WA-V 200 “G” | 230 | 2.500 |
WA-V 250 “G” | 450 | 3.000 |
WA-V 300 “G” | 450 | 3.000 |
WA-V 350 “G” | 450 | 3.000 |
WA-V 380 “G” | 450 | 3.000 |
WA-V 400 “G” | 450 | 3.000 |
WA-V 450 “G” | 550 | 3.000 |
WA-V 500 “G” | 550 | 3.490 |
WA-V 600 “G” | 550 | 3.490 |
WA-V 620 “G” | 1.000 | 3.500 |
WA-V 640 “G” | 1.000 | 3.500 |
WA-V 660 “G” | 1.030 | 3.500 |
WA-V 700 “G” | 1.030 | 3.620 |
Volvo Penta Generator |
Width mm |
Height mm |
WA-V 85 “G” | 930 | 1.713 |
WA-V 100 “G” | 930 | 1.827 |
WA-V 130 “G” | 930 | 1.732 |
WA-V 150 “G” | 1.035 | 1.683 |
WA-V 180 “G” | 1.035 | 1.845 |
WA-V 200 “G” | 1.035 | 1.845 |
WA-V 250 “G” | 1.200 | 1.834 |
WA-V 300 “G” | 1.200 | 2.160 |
WA-V 350 “G” | 1.200 | 2.163 |
WA-V 380 “G” | 1.200 | 2.141 |
WA-V 400 “G” | 1.200 | 2.141 |
WA-V 450 “G” | 1.200 | 2.100 |
WA-V 500 “G” | 1.300 | 2.097 |
WA-V 600 “G” | 1.300 | 2.097 |
WA-V 620 “G” | 1.330 | 2.506 |
WA-V 640 “G” | 1.330 | 2.506 |
WA-V 660 “G” | 1.330 | 2.816 |
WA-V 700 “G” | 1.330 | 2.816 |
Volvo Penta Generator | Weight KG |
WA-V 85 “G” | 1.240 |
WA-V 100 “G” | 1.300 |
WA-V 130 “G” | 1.480 |
WA-V 150 “G” | 1.580 |
WA-V 180 “G” | 1.850 |
WA-V 200 “G” | 1.820 |
WA-V 250 “G” | 2.050 |
WA-V 300 “G” | 2.800 |
WA-V 350 “G” | 2.850 |
WA-V 380 “G” | 2.940 |
WA-V 400 “G” | 2.940 |
WA-V 450 “G” | 3.180 |
WA-V 500 “G” | 3.580 |
WA-V 600 “G” | 3.950 |
WA-V 620 “G” | 4.300 |
WA-V 640 “G” | 4.350 |
WA-V 660 “G” | 4.500 |
WA-V 700 “G” | 4.770 |
“S” Silenced
Silenced version (with insulation) “S”
Volvo Penta Gen Set Silent | Fueltank L |
db(A)* 7 Meter |
WA-V 85 “S” | 220 | 72 |
WA-V 100 “S” | 220 | 72 |
WA-V 130 “S” | 220 | 72 |
WA-V 150 “S” | 360 | 72 |
WA-V 180 “S” | 360 | 70 |
WA-V 200 “S” | 360 | 70 |
WA-V 250 “S” | 360 | 72 |
WA-V 300 “S” | 530 | 72 |
WA-V 350 “S” | 530 | 72 |
WA-V 380 “S” | 530 | 72 |
WA-V 400 “S” | 530 | 72 |
WA-V 450 “S” | 530 | 72 |
WA-V 500 “S” | 1.000 | 75 |
WA-V 600 “S” | 1.000 | 76 |
WA-V 620 “S” | 1.000 | 77 |
WA-V 640 “S” | 1.000 | 77 |
WA-V 660 “S” | 1.000 | 77 |
WA-V 700 “S” | 1.000 | 77 |
* db(A) measured at 7 meters as the average of all-round measurement at 7 measuring points
Volvo Penta Gen Set Silent |
Length mm |
Width mm |
WA-V 85 “S” | 2.950 | 1.110 |
WA-V 100 “S” | 2.950 | 1.110 |
WA-V 130 “S” | 2.950 | 1.110 |
WA-V 150 “S” | 3.600 | 1.350 |
WA-V 180 “S” | 3.600 | 1.350 |
WA-V 200 “S” | 3.600 | 1.350 |
WA-V 250 “S” | 3.600 | 1.350 |
WA-V 300 “S” | 4.200 | 1.600 |
WA-V 350 “S” | 4.200 | 1.600 |
WA-V 380 “S” | 4.200 | 1.600 |
WA-V 400 “S” | 4.200 | 1.600 |
WA-V 450 “S” | 4.200 | 1.600 |
WA-V 500 “S” | 4.860 | 2.060 |
WA-V 600 “S” | 4.860 | 2.060 |
WA-V 620 “S” | 4.860 | 2.060 |
WA-V 640 “S” | 4.860 | 2.060 |
WA-V 660 “S” | 4.860 | 2.060 |
WA-V 700 “S” | 4.860 | 2.060 |
Volvo Penta Gen Set Silent |
Height mm |
Weight KG |
WA-V 85 “S” | 1.760 | 1.680 |
WA-V 100 “S” | 1.760 | 1.840 |
WA-V 130 “S” | 1.760 | 1.980 |
WA-V 150 “S” | 2.040 | 2.180 |
WA-V 180 “S” | 2.040 | 2.850 |
WA-V 200 “S” | 2.040 | 2.850 |
WA-V 250 “S” | 2.040 | 3.018 |
WA-V 300 “S” | 2.245 | 4.200 |
WA-V 350 “S” | 2.245 | 4.320 |
WA-V 380 “S” | 2.245 | 4.660 |
WA-V 400 “S” | 2.145 | 4.660 |
WA-V 450 “S” | 2.145 | 4.660 |
WA-V 500 “S” | 2.630 | 6.260 |
WA-V 600 “S” | 2.630 | 6.260 |
WA-V 620 “S” | 2.630 | 6.380 |
WA-V 640 “S” | 2.630 | 6.380 |
WA-V 660 “S” | 2.630 | 6.800 |
WA-V 700 “S” | 2.585 | 7.100 |
All data in basic model or series delivery
Basic equipment Volvo Penta generator
Power generator: The complete power generator is mounted on a steel base frame. On the steel base frame are specially designed devices, for lifting with a crane or Forklift. The diesel engine and the alternator are connected to a SAE-flange, that even a longer period of operation no possibility of an adjustment exists. The daily fuel tank is integrated in the steel base frame. The starter batteries of 12 or 24 volts are fixed on the steel base frame. Preheating-system 230 Volt DC.
Engine: Volvo industrial diesel 4-stroke direct injection, watercooled 1.500 rpm (50 Hz). Low oil and fuel consumption with long maintenance intervals make a very economic engine application.
Alternator: Mecc Alte alternator, brushless self-exciting, self-regulating with electronic voltage regulator (AVR) according to VDE 0530, 400/230 volts, 4-pole, insulation class H.
Control Panel: Manual start-stop-system with engine shutdown during monitoring, when low oil pressure (LOP), High temperate (HWT) and overspeed. Alternator switch, 3-pole with thermal and magnetic protection. Frequency meter, hours counter, voltmeter, ampere meter, optical and acoustic alarm. Electronic engine speed governor, AMF automatic control panel with ATS, for parallel operation with the mains supply or peak looping operation.
Tank: 24h fuel tank, automatic fuel-fill-system.
Trailer: 1 or 2 axle trailer.
Options: For all power generator is a wide range of accessories available.
Technical changes: We keep ahead.