Iveco power generators series WA-I 30-500 kVA

Our Iveco power generators – 1.500 r.p.m – 50 Hz and 1.800 r.p.m with 60 Hz

Power  Generator
kVA 100 %
PRP*
Motortype
WA-I 30 30 F 32 AM 1 A
WA-I 45
41 F 32 SM 1 A
WA-I 50 50 F 32 TM 1 A
WA-I 60 60 N 45 SM 1 A
WA-I 75 73 N 45 SM 2 A
WA-I 100 98 N 45 TM 2 A
WA-I 135 131 N 67 TM 2 A
WA-I 160 159 N 67 TM 3 A
WA-I 180 182 N 67 TE 2 A
WA-I 200 200 N 67 TE 2 A
WA-I 250 250 C 87 TE 1 D
WA-I 305 300 C 10 TE 1 D
WA-I 350 350 CE 13 TE 2 A
WA-I 400 400 C 13 TE 3 A
WA-I 500 500 C 13 TE 7

*Prime Power PRP. Maximum power for variable load, no time limit per year. The average 24 hours operation should not exceed 80% of that power. For control purposes an thrust harder Maschinery is an overload of 10% for 1 hour within 12 hours permitted. Mode according to ISO 8528. The maintenace is to be considered.

Power generator
Power
KWm.
Consumption
100 % Last PRP
WA-I 30 28,5 KW 8,30 L/h
WA-I 45
37,7 KW 10,60 L/h
WA-I 50 46,8 KW 12,60 L/h
WA-I 60 53,5 KW 13,70 L/h
WA-I 75 66,0 KW 17,10 L/h
WA-I 100 87,0 KW 22,00 L/h
WA-I 135 114 KW 29,30 L/h
WA-I 160 138,0 KW 36,00 L/h
WA-I 180 175,0 KW 44,00 L/h
WA-I 200 175,0 KW 44,00 L/h
WA-I 250 232,0 KW 58,5 L/h
WA-I 305 264,0 KW 62,80 L/h
WA-I 350 300,0 KW 70,00 L/h
WA-I 400 352,0 KW 87,50 L/h
WA-I 500 421,0 KW 109,00 L/h

 

“G” on sled frame

stromerzeuger-iveco-gStationary version (open type) sled frame “G”

 

 

 

 

Power generator
Fueltank
  L
Length
mm
WA-I 30 “G”
120
1.850
WA-I 45 “G”
120
1.850
WA-I 50 “G”
145
2.150
WA-I 60 “G”
145
2.150
WA-I  75 “G”
145
2.150
WA-I 100 “G”
145
2.150
WA-I 135 “G”
250
2.900
WA-I 160 “G”
250
2.900
WA-I 180 “G”
250
2.900
WA-I 200 “G”
250
2.900
WA-I 250 “G”
445
3.000
WA-I 305 “G”
597
3.310
WA-I 350 “G”
597
3.310
WA-I 400 “G”
597
3.310
WA-I 500 “G”
558
3.490

 

Power generator
Width
mm
Height
mm
WA-I 30 “G”
780
1.500
WA-I 45 “G”
780
1.500
WA-I 50 “G”
780
1.500
WA-I 60 “G”
780
1.500
WA-I 75 “G”
780
1.500
WA-I 100 “G”
780
1.500
WA-I 135 “G”
900
1.603
WA-I 160 “G”
900
1.603
WA-I 180 “G”
900
1.604
WA-I 200 “G”
900
1.634
WA-I 250 “G”
1.170
1.793
WA-I 305 “G”
1.390
1.796
WA-I 350 “G”
1.390
1.876
WA-I 400 “G”
1.390
1.876
WA-I 500 “G”
1.300
2.097

 

Power generator
Weight
KG
WA-I 30 “G”
786
WA-I 45 “G”
714
WA-I 50 “G”
868
WA-I 60 “G”
970
WA-I 75 “G”
995
WA-I 100 “G”
1.125
WA-I 135 “G”
1.625
WA-I 160 “G”
1.625
WA-I 180 “G”
1.650
WA-I 200 “G”
1.695
WA-I 250 “G”
2.600
WA-I 305 “G”
2.825
WA-I 350 “G”
2.980
WA-I 400 “G”
3.165
WA-I 500 “G”
3.670

 

“S” Silenced

stromerzeuger-iveco-sSilenced version (with insulation) “S”

 

 

 

Power generator
Fueltank
L
db (A) *
 7 Meter
WA-I 30″S”
100
68
WA-I 45″S”
100
62
WA-I 50 “S”
130
64
WA-I 60 “S”
288
69
WA-I 75 “S”
288
69
WA-I 100 “S”
288
69
WA-I 135 “S”
450
68
WA-I 160 “S”
450
68
WA-I 180 “S”
450
68
WA-I 200 “S”
450
68
WA-I 250 “S”
449
68
WA-I 305 “S”
597
68
WA-I 350 “S”
597
68
WA-I 400 “S”
597
68
WA-I 500 “S”
534
70

* db(A) measured at 7 meters as the average of all-round measurement at 7 measuring points

 

Power generator
Length
mm
Width
mm
WA-I 30″S”
2.100
975
WA-I 45″S”
2.100
975
WA-I 50 “S”
2.300
1.050
WA-I 60 “S”
2.750
1.100
WA-I 75 “S”
2.750
1.100
WA-I 100 “S”
2.750
1.100
WA-I 135 “S”
3.300
1.200
WA-I 160 “S”
3.300
1.200
WA-I 180 “S”
3.300
1.200
WA-I 200 “S”
3.300
1.200
WA-I 250 “S”
3.800
1.400
WA-I 305 “S”
4.100
1.600
WA-I 350 “S”
4.100
1.600
WA-I 400 “S”
4.100
1.600
WA-I 500 “S”
4.200
1.600

 

Power generator
Height
mm
Weight
KG
WA-I 30″S”
1.349
991
WA-I 45″S”
1.349
1.044
WA-I 50 “S”
1.458
1.296
WA-I 60 “S”
1.760
1.538
WA-I 75 “S”
1.760
1.564
WA-I 100 “S”
1.760
1.690
WA-I 135 “S”
1.958
2.362
WA-I 160 “S”
1.958
2.400
WA-I 180 “S”
1.958
2.443
WA-I 200 “S”
1.958
2.517
WA-I 250 “S”
2.290
3.701
WA-I 305 “S”
2.200
4.028
WA-I 350 “S”
2.200
4.191
WA-I 400 “S”
2.200
4.376
WA-I 500 “S”
2.245
4.850

All data in basic model or series delivery

 

Basic equipment Iveco power generator

GenSet: The complete gen set is mounted on a steel base frame. On the steel base frame are specially designed devices, for lifting with a crane or Forklift. The diesel engine and the alternator are connected to a SAE-flange, that even a longer period of operation no possibility of an adjustment exists. The daily fuel tank is integrated in the steel base frame. The starter batteries of 12 or 24 volts are fixed on the steel base frame. Preheating-system 230 Volt DC.

Engine: Iveco industrial diesel 4-stroke direct injection, liquid cooled 1.500 rpm (50 Hz). Low oil and fuel consumption with long maintenance intervals make a very economic engine application.

Alternator: Mecc Alte alternator, brushless self-exciting, self-regulating with electronic voltage regulator (AVR) according to VDE 0530, 400/230 volts, 4-pole, insulation class H.

Control Panel: Manual start-stop-system with engine shutdown during monitoring, when low oil pressure (LOP), High temperate (HWT) and overspeed. Alternator switch, 3-pole with thermal and magnetic protection. Frequency meter, hours counter, voltmeter, ampere meter, optical and acoustic alarm. Electronic engine speed governor, AMF automatic control panel with ATS, for parallel operation with the mains supply or peak looping operation.

Tank: 24h fuel tank, automatic fuel-fill-system.

Trailer: 1 or 2 axle trailer.

Options: For all power generator is a wide range of accessories available.

Technical changes: We keep ahead.