delivery contents:
New, soundproofed (69 db"A" (+/- 2.4) as the mean value of an all-round measurement at 7 measuring points) emergency power generator as backup power supply, designed for continuous operation around the clock.
The silencer hood is modular with generous doors for maintenance.
The built-in emergency power control, manufacturer Comap, type IG 200 is designed for uninterrupted reverse synchronization overlapping synchronization with control of your on-site network generator switchover.
Internal day tank (800 liters) in the base frame with drip tray. Optionally with leakage monitoring
Fuel consumption & data according to Scania data sheet:
Consumption at 25% approx. 26.00 liters / hour | sufficient for approx. 30.7 hours
Consumption at 50% approx. 50 liters / hour | sufficient for approx. 16 hours
Consumption at 75% approx. 71 liters / hour | sufficient for approx. 11.2 hours
Consumption at 100% approx. 100 liters / hour | enough for about 8 hours
-/-
Amount of lubricating oil: 38 liters
Lubricating oil consumption: 0.35 liters / hour max.
Amount of cooling water: 54 liters
-/-
Heat balance at 100% PRP performance:
Exhaust gas: 344 kW
Cooling water and oil 158 kW
Radiation 39 kW
LLK charge air cooling intercooler 104 kW
-/-
Exhaust volume: 36 KG / minute
Exhaust gas temperature 563°C
Maximum back pressure: 10 kPA (0.1 bar)